What does the LCD initial screen mean?
You can generally view the measured values and all the alarms on this screen, and can view and change data using menu by and the FUNCTION key. If you do not press any key for 10 minutes, the screen goes off automatically. By pressing any key, the LCD lights up again.
What is the command F0 used for?
After pressing F0, you must put in a password. If you put in the password '000000', you can change any individual setting, all from one screen.
What is Current State F1?
By pressing F1, you can view the current rectifier settings as well as alarm history data
What is the EDIT F2?
With EDIT F2, you can configure the system, set the upper/lower values, configure the system operations, set the output voltage, etc.
What is Time Change F3?
With F3, you can change the current time.
What is Sound (On) F4?
With F4, you can activate and deactivate audible alarm (sound).
What is System State F5?
With F5, you can view data and alarms stated in real time for AC distributor, DC controller, rectifier units, and the battery.
What should I do when load sharing is not activated between rectifier modules?
There are three internal variable resistors on the front plate of the rectifier module. Compare the load sharing state and balance the load, turning the middle variable resistor clockwise using a crosshead screwdriver. If the load is not shared even though you try to adjust it, establish the output voltage again on the control unit or check the load sharing state again by turning the rectifier off and on. If the rectifier module does not work even after turning it off and on, you have to replace the rectifier module. 
What should I do when the measured voltage is different between rectifier modules?
This situation means that the sensing reference of measuring voltage is low. You can complement the value by adjusting the first variable resistor using a cross-head screwdriver.
What should I do when the AD alarm occurs?
This alarm sounds when the upper/lower limit values are wrongly specified for input/output voltage and current; when the setting value is correct, but the actually measured value is different from the measurement data; when the extension rack is used, and a communication error occurs between the main rack and extension rack. For the AD alarm, consult with the customer service representative.
What range is the input voltage?
It is 418~342V for 380V and 242~198V for 220V.
What is the variable range of the output voltage?
The output voltage can be specified in the range of 56~48V, and the current limit can be specified with 90~110%.
What should I do when the DC alarm occurs?
If a fuse for load and battery has blown, check the fuse number whose error has occurred on the DC controller screen and remove the cause of error. If no fuse has blown but the alarm sounds, you have to replace the DSRC-ADI board.
What are the RF alarms?
AF, TH, OV, UV, MD, and CL problems of the rectifier unit activate the alarm.
What should I do in Fail in the AF (ac fail)?
This occurs when the AC input is abnormal in the unit. If the main input is normal but a specific unit generates this alarm, switch off the unit and replace it.
What should I do in Fail in the TH (thermal)?
This over-temperature alarm occurs when the internal temperature is higher than 130 degrees. You have to cool or replace the unit.
What should I do in Fail in the OV (over volt)?
This output high voltage alarm occurs when the output voltage of the rectifier unit is greater than the upper limit value. Press the reset switch of the unit or turn the input switch OFF/ON. If the alarm does not disappear even after these measures, you have to replace the unit.
What should I do in Fail in the UV (under voltage)?
This output low voltage alarm occurs when the output voltage of the rectifier unit is lower than the lower limit value and when the output interval is instantaneously short. Press the reset switch of the unit. If the alarm does not stop even after these measures, you have to replace the unit.
What does Fail in the MD (hold mode) indicate?
The operator has made the state Standby, it is regarded as normal.
What does Fail in the CF (communication fail) indicate?
There is a communication error between the rectifier unit and the control panel. Consult with the customer service representative.
What does Fail in the NC (no connection) indicate?
It occurs when the unit input switch gets disconnected during normal operation or when the operator was forced to disconnect the switch.
What does Fail in the CL (current limit) indicate?
It occurs when the current of unit is greater than 100%.
When does the MJ (major) alarm occur?
It occurs when the fuse for output voltage, output current, battery or load has blown out.
When does the MN (minor) alarm occur?
It occurs if there is an error in input voltage, input current, rectifier unit.
What methods are used to generate alarms?
Voltage method and contact point methods are alternatively used: the voltage method has 0V for normal working and DC 52V for an error, and the contact point method has low impedance (L) for normal working and high impedance (H) for an error.
| Home | Company | News | Products | Support | Financial | Glossary |