Pressing the Function key on the DCCR program indication window shows a broken value. What should I do for the rectifier not in service?
First, you have to take emergency measures because the board of DC control panel has an error. Open the air vent cover on the top rectifier rack ; switch off the toggle switch on the HTEM-102 board; and consult with the customer service representative. In this case, the rectifier output voltage of rectifier is DC -52V and the load can be unbalanced.
The LED does not light up on the DCCR, but the rectifier error alarm is detected in the electric power supply room or the switching system room. What should I do?
Check the alarm system of the electric power supply room and the switching system room. If there is no error, there may be an error in the DCCR HTFT alarm board, so consult with the customer service representative.
All the rectifier racks are normal, but the error LED lights up in the DC control panel. What should I do?
Check if a red LED lights up on each rectifier module. Power off each rectifier module with the red LED light, and consult with the customer service representative.
During a power failure, the battery supplies the power. However, the DC output voltage goes down rapidly. What should I do?
DongAh Elecomm rectifiers are connected in parallel with the battery. The voltage drop can occur due to a battery error. Consult with the battery provider.