OUTPUT
Floating
Voltage: 48V ~ 58V adjustable
Rated
Max. Current: 25A/Module, 200A/Rack
Current
Limit: 120A (Module), 100~120% (Rack)
Regulation:
±0.5%
Noise:
< 2mV (psophometric noise)
<
10mV rms
<
100mV p-p (peak to peak)
<
45 dBA (acoustic noise)
Load
Sharing: Forced load sharing
Protection:
Circuit breakers
Over
Voltage: only faulty module shut down
Over
Current: automatic shutdown if output current rises over 115%
and
output voltage drops to 25V
Thermal
protection: shut down at abnormally high temperature
Surge:
6KV (1.2x50 ),
3KA (8x20 )
|