| OUTPUT
Floating
Voltage: 27V ~ 57V adjustable
Rated
Max. Current: 50A/Module, 500A/Rack
Current
Limit: 110 ~ 130%
Regulation: ±0.5%
Noise:
< 2mV (psophometric noise)
<10mV
rms
<100mV
p-p (peak to peak)
Load
sharing: Forced load sharing within ±10% full load
Protection:
Circuit breakers
Over
voltage: only faulty module shut down
Over
current: Short circuit protection
Thermal
protection: shut down at abnormally high temperature
Surge:
6KV (1.2x50 ),
3KA (8x20 )
|